10.7 - Type III Memorization Sheet
Module: Universal Review and Mock Examinations
Purpose: One-page-target rapid review of the highest-priority Type III facts before Universal mock examinations
Covers: Type III material consolidated from Sections 9.1–9.10
Regulatory and safety verification basis: Current Module 9 material verified August 13, 2026
Use: Memorize the low-pressure fundamentals, purge-unit logic, leak-test limits, recovery sequence, freeze prevention, oil-service values, vapor-first charging, evacuation requirement, and safety distinctions below; return to Module 9 when a condition or exception is unclear
1. Type III = Low-Pressure Appliances
Type III certification applies to covered:
LOW-PRESSURE APPLIANCES
Current Section 608 classification:
LIQUID-PHASE SATURATION PRESSURE
<45 psia at 104°F
→ LOW PRESSURE
→ TYPE III
Common Type III Examples
- Low-pressure centrifugal chillers.
- Low-pressure absorption chillers.
- Other appliances that satisfy the current low-pressure refrigerant classification.
Exam Traps
LARGE CHILLER
≠
AUTOMATICALLY TYPE III
LOW SIDE
≠
LOW-PRESSURE APPLIANCE
CHILLER
≠
AUTOMATICALLY TYPE III
Pressure classification controls.
2. Why Type III Is Different
Many low-pressure chillers operate with refrigerant-side pressure:
BELOW ATMOSPHERIC PRESSURE
Therefore:
AIR + MOISTURE
→ CAN LEAK INTO THE APPLIANCE
instead of refrigerant always leaking outward.
Consequences of Air and Moisture Infiltration
- Noncondensables accumulate.
- Head pressure can increase.
- Purge-unit operation can increase.
- Moisture can contaminate refrigerant and lubricant.
- Corrosion and acid formation can become concerns.
- Water entering the refrigerant side creates major freeze-risk problems during deep recovery.
Important Distinction
LOW-PRESSURE APPLIANCE
≠
EVERY POINT ALWAYS UNDER VACUUM
Some conditions, shutdown states, or service procedures can place parts of the appliance at positive gauge pressure.
3. Major Type III Components
Know the function of:
- Evaporator.
- Condenser.
- Centrifugal compressor.
- Purge unit.
- Rupture disc / pressure-relief protection.
- Water boxes.
- Evaporator charging valve.
- Oil system, when the chiller uses one.
- Refrigerant monitor.
Fast Component Logic
EVAPORATOR
→ chilled-water heat exchanger
→ low refrigerant-side region
→ charging connection used in Type III exam procedure
CONDENSER
→ rejects heat
→ condenses refrigerant vapor
PURGE UNIT
→ removes noncondensables
→ minimizes refrigerant loss
RUPTURE DISC
→ non-reclosing emergency pressure relief
4. Purge Units
Because air can enter a low-pressure chiller:
NONCONDENSABLES
→ COLLECT
→ MUST BE REMOVED
Purge-Unit Purpose
PURGE UNIT
→ REMOVE AIR / NONCONDENSABLES
→ MINIMIZE REFRIGERANT LOSS
A purge unit is not the recovery machine used to recover the entire chiller charge.
Frequent Purging
FREQUENT PURGE OPERATION
→ POSSIBLE AIR INFILTRATION / LEAK
It is a diagnostic clue, not proof of the exact leak location.
Purge and Head Pressure
Noncondensables can:
RAISE CONDENSER / HEAD PRESSURE
and reduce system efficiency.
Moisture Clue
Excess moisture collected or indicated by the purge system can suggest:
POSSIBLE WATER-SIDE / TUBE LEAKAGE
Further diagnosis is required.
Exam Trap
PURGE UNIT
≠
LICENSE TO VENT REFRIGERANT
Refrigerant in purge discharge must be controlled according to the applicable system design and refrigerant-management requirements.
5. Low-Pressure Leak Detection and Pressurization
Preferred General Concept
Because the appliance may normally be under vacuum:
RAISE PRESSURE CAREFULLY
→ THEN LEAK CHECK
Controlled methods taught in Module 9 include:
- Warm water.
- Heater blankets or other controlled warming where permitted.
- Dry nitrogen where the approved procedure permits it.
Type III Exam-Preparation Maximum
10 psig
→ LOW-PRESSURE CHILLER LEAK-TEST MAXIMUM
Treat this as the Type III examination-preparation maximum used in this course.
It is not a target pressure that must always be reached.
Pressure-Control Rule
CONTROLLED PRESSURIZATION
→ DO NOT EXCEED SAFE / SPECIFIED LIMIT
Open-Drive Shaft Seal
For an open-drive low-pressure machine:
SHAFT SEAL
→ IMPORTANT LEAK-CHECK LOCATION
Tube-Leak Concern
A tube leak can allow:
WATER
→ ENTER REFRIGERANT CIRCUIT
This becomes especially dangerous during recovery because decreasing refrigerant pressure lowers saturation temperature and can freeze water.
6. Recovery Sequence
High-priority Type III recovery sequence:
REMOVE ACCESSIBLE BULK LIQUID FIRST
→ RECOVER REMAINING VAPOR
→ CONTINUE TO REQUIRED ENDPOINT
→ ISOLATE / WAIT / CHECK PRESSURE REBOUND
Why Liquid First?
LIQUID
→ contains much more refrigerant mass per unit volume
→ faster bulk refrigerant removal
Vapor Still Matters
After liquid removal:
A LARGE VAPOR MASS MAY REMAIN
Therefore:
NO VISIBLE LIQUID
≠
RECOVERY COMPLETE
Recovery-Machine Condenser
During vapor recovery:
RECOVERY-MACHINE CONDENSER
→ rejects heat
→ helps condense recovered refrigerant
Adequate cooling is essential.
Traditional Recovery-Equipment Values
10 psig
→ LOW-PRESSURE RECOVERY-UNIT
HIGH-PRESSURE CUTOUT
15 psig
→ LOW-PRESSURE RECOVERY-VESSEL
RUPTURE-DISC EXAM VALUE
These values refer to different components.
Exam Trap
15 psig recovery-vessel rupture disc
≠
universal chiller relief-device rating
7. Freeze Prevention During Recovery
As chiller pressure falls:
REFRIGERANT SATURATION TEMPERATURE FALLS
If water remains in the heat-exchanger tubes:
DEEP RECOVERY
→ LOW REFRIGERANT TEMPERATURE
→ WATER CAN FREEZE
→ TUBE DAMAGE POSSIBLE
Normal Water Management
During normal recovery when the system is configured for circulation:
CHILLED-WATER CIRCULATION
+
CONDENSER-WATER CIRCULATION / MANAGEMENT
→ REDUCE FREEZE RISK
The traditional Type III recovery relationship taught in Module 9 is:
CHILLER WATER PUMPS
+
RECOVERY COMPRESSOR
+
RECOVERY-CONDENSER COOLING WATER
→ OPERATE AS REQUIRED
Suspected Tube Leak
If tube leakage is suspected under the Type III exam procedure:
DRAIN EVAPORATOR WATER SIDE
+
DRAIN CONDENSER WATER SIDE
BEFORE RECOVERY
This reduces the chance that water will be pulled into the low-pressure refrigerant circuit and freeze.
Charging Freeze Trap
LIQUID REFRIGERANT
+
DEEP VACUUM
→ RAPID FLASHING
→ STRONG COOLING
→ WATER-FREEZING RISK
Therefore:
DO NOT BEGIN DEEP-VACUUM RECHARGE
WITH BULK LIQUID
8. Refrigerant in Oil
Traditional oil-lubricated low-pressure chillers can retain refrigerant dissolved in compressor oil.
As pressure falls:
REFRIGERANT
→ COMES OUT OF SOLUTION
→ ADDITIONAL VAPOR LOAD
Therefore:
APPARENT RECOVERY ENDPOINT
→ PRESSURE MAY REBOUND
Oil-Heating Exam Value
130°F
→ TYPE III OIL-HEATING EXAM VALUE
BEFORE OIL REMOVAL
The purpose is to help drive dissolved refrigerant out of the oil before removal.
Current Oil-Change Pressure Provision
NO HIGHER THAN 5 psig
→ CURRENT SPECIAL OIL-CHANGE OPENING PROVISION
Do Not Confuse
130°F
→ OIL TEMPERATURE
5 psig
→ OIL-CHANGE PRESSURE LIMIT
25 mm Hg absolute
→ NORMAL TYPE III FINAL RECOVERY ENDPOINT
They are three different concepts.
Modern Equipment Reminder
Not every modern centrifugal chiller uses a conventional oil system.
The traditional oil-service procedure remains important because it is part of Type III examination preparation.
9. Recharging Low-Pressure Systems
Charging Connection
Type III exam emphasis:
EVAPORATOR CHARGING VALVE
→ MANUFACTURER-DESIGNATED LOW REFRIGERANT-SIDE
CHARGING CONNECTION
The phrase lowest access point does not mean:
ANY FITTING PHYSICALLY CLOSEST TO THE FLOOR
Use the designated refrigerant charging connection.
Vapor First
When a low-pressure chiller is deeply evacuated:
INTRODUCE VAPOR FIRST
Why?
VAPOR ADDED
→ PRESSURE RISES
→ SATURATION TEMPERATURE RISES
→ FREEZE RISK DECREASES
Then:
WHEN SAFE UNDER THE APPROVED PROCEDURE
→ TRANSITION TO LIQUID CHARGING
Critical Memory Rule
DEEP VACUUM
→ VAPOR FIRST
→ LIQUID LATER
Blend Distinction
If a refrigerant blend must leave its source container as liquid to prevent fractionation, that does not cancel the Type III vapor-first requirement.
The technician can:
REMOVE BLEND FROM SOURCE AS LIQUID
→ CONTROL / VAPORIZE IT AS REQUIRED
→ INTRODUCE VAPOR FIRST INTO DEEPLY EVACUATED CHILLER
Exam Trap
BLEND CHARGED FROM SOURCE AS LIQUID
≠
BULK LIQUID DIRECTLY INTO DEEP VACUUM
10. Type III Evacuation Requirement
Current Table 1 requirement for a low-pressure appliance:
25 mm Hg absolute
Important Features
The Type III value is:
- The same for recovery equipment manufactured before November 15, 1993.
- The same for recovery equipment manufactured on or after November 15, 1993.
- Not changed by a 200-lb charge boundary.
Unit Trap
25 mm Hg absolute
≠
25 in. Hg vacuum
For absolute-pressure scales:
SMALLER NUMBER
→ DEEPER VACUUM
Pressure-Rebound Check
After reaching the required recovery vacuum:
ISOLATE
→ WAIT A FEW MINUTES
→ OBSERVE PRESSURE
A pressure rise can indicate:
- Residual liquid refrigerant evaporating.
- Refrigerant coming out of oil.
- Moisture / outgassing during post-service vacuum evaluation.
- Leakage.
For Type III recovery exam questions, residual refrigerant and refrigerant in oil are especially important clues.
Qualifying Non-Major Opening
When all current conditions are satisfied:
LOW-PRESSURE APPLIANCE
→ MAY BE PRESSURIZED TO
NO HIGHER THAN 0 psig
BEFORE OPENING
Leak Prevents Normal Endpoint
If a leak prevents reaching the prescribed evacuation level without substantial contamination:
ISOLATE WHERE POSSIBLE
Then:
NON-LEAKING PORTION
→ NORMAL REQUIRED LEVEL
LEAKING PORTION TO BE OPENED
→ LOWEST ATTAINABLE LEVEL
→ NOT ABOVE 0 psig
11. Type III Safety and Machinery Rooms
Rupture Disc
RUPTURE DISC
→ EMERGENCY PRESSURE RELIEF
→ NON-RECLOSING
After rupture, it must be replaced appropriately.
Relief-Valve Arrangement
For Type III exam preparation:
DO NOT SIMPLY INSTALL
TWO ORDINARY INDEPENDENT RELIEF VALVES IN SERIES
AS A SUBSTITUTE FOR A PROPER RELIEF SYSTEM
Approved engineered arrangements can differ; follow equipment design, applicable code, and manufacturer requirements.
Refrigerant Monitor Versus Oxygen Monitor
REFRIGERANT MONITOR
→ measures refrigerant concentration
OXYGEN MONITOR
→ measures oxygen concentration
One does not automatically replace the other.
Oxygen Deficiency
OSHA general-industry terminology:
OXYGEN <19.5%
→ OXYGEN-DEFICIENT ATMOSPHERE
Machinery Room Versus Confined Space
MACHINERY ROOM
≠
AUTOMATICALLY OSHA CONFINED SPACE
Individual spaces such as:
- Pits.
- Vessels.
- Water boxes.
- Other enclosures.
must be evaluated by their actual configuration and hazards.
Water-Side Hazards
Before opening water-side equipment:
STOP / ISOLATE HAZARDOUS ENERGY
→ VERIFY PRESSURE IS RELIEVED
→ CONTROL UNEXPECTED PUMP STARTUP
A stopped pump does not prove:
WATER-SIDE PRESSURE = 0
Static head or trapped pressure may remain.
Code Review
NEWEST PUBLISHED STANDARD
≠
AUTOMATICALLY ENFORCEABLE IN EVERY JURISDICTION
Follow:
- Locally adopted code.
- Authority having jurisdiction (AHJ).
- Manufacturer instructions.
- Employer safety procedures.
12. Type III Numbers to Know Cold
| Number / Value | Type III Meaning |
|---|---|
| <45 psia at 104°F | Current low-pressure appliance classification |
| 10 psig | Type III leak-test maximum used in exam preparation |
| 10 psig | Traditional low-pressure recovery-unit high-pressure cutout |
| 15 psig | Traditional low-pressure recovery-vessel rupture-disc exam value |
| 130°F | Type III oil-heating exam value |
| 5 psig | Current special oil-change opening pressure limit |
| 25 mm Hg absolute | Current normal Type III Table 1 evacuation endpoint |
| 0 psig | Current qualifying non-major opening / leaking-section ceiling when applicable |
| 19.5% oxygen | OSHA oxygen-deficient threshold used in the Module 9 safety discussion |
The Type III Number Separation
10 psig
→ LEAK-TEST EXAM MAXIMUM
10 psig
→ RECOVERY-UNIT CUTOUT
15 psig
→ RECOVERY-VESSEL RUPTURE DISC
130°F
→ OIL HEATING
5 psig
→ OIL-CHANGE OPENING
25 mm Hg ABSOLUTE
→ FINAL NORMAL RECOVERY ENDPOINT
13. Highest-Priority Type III Exam Traps
Trap 1
Low pressure
→ refrigerant always leaks outward
Wrong. Air and moisture can leak inward when the appliance is below atmospheric pressure.
Trap 2
Purge unit
→ recovery machine for entire chiller
Wrong.
Trap 3
Frequent purging
→ normal proof that no leak exists
Wrong. Frequent purging can indicate air infiltration.
Trap 4
Remove vapor first
Wrong when accessible bulk liquid is available.
Type III recovery:
LIQUID FIRST
→ VAPOR SECOND
Trap 5
No liquid visible
→ recovery complete
Wrong. A substantial vapor mass and refrigerant in oil may remain.
Trap 6
Stop all water flow during deep recovery
Wrong for the normal recovery arrangement. Water must be circulated or otherwise managed to prevent freezing.
Trap 7
Suspected tube leak
→ continue normal water circulation without evaluation
Wrong. Under the Type III exam procedure, drain the evaporator and condenser water sides before recovery.
Trap 8
Deep vacuum
→ add bulk liquid first
Wrong.
VAPOR FIRST
→ LIQUID LATER
Trap 9
25 mm Hg absolute
→ 25 in. Hg vacuum
Wrong.
Trap 10
15 psig
→ universal chiller rupture-disc rating
Wrong. The 15-psig exam value belongs to the low-pressure recovery vessel.
Trap 11
Refrigerant monitor
→ oxygen monitor
Wrong. They measure different quantities.
Trap 12
Machinery room
→ automatically confined space
Wrong.
Trap 13
Water pump stopped
→ water pressure is zero
Wrong.
14. Type III Final Memory Map
TYPE III
→ LOW PRESSURE
→ <45 psia @ 104°F
BELOW ATMOSPHERE
→ AIR + MOISTURE IN
PURGE UNIT
→ REMOVE NONCONDENSABLES
→ FREQUENT PURGING MAY SIGNAL INFILTRATION
LEAK TEST
→ CONTROLLED PRESSURIZATION
→ 10 psig EXAM MAXIMUM
RECOVERY
→ LIQUID FIRST
→ VAPOR SECOND
→ CONDENSER COOLING
→ WATER MANAGEMENT
RECOVERY UNIT CUTOUT
→ 10 psig
RECOVERY-VESSEL RUPTURE DISC
→ 15 psig
FREEZE PREVENTION
→ CIRCULATE / REMOVE WATER AS REQUIRED
SUSPECTED TUBE LEAK
→ DRAIN EVAPORATOR + CONDENSER WATER SIDES
OIL
→ REFRIGERANT CAN REMAIN DISSOLVED
→ 130°F EXAM VALUE
→ OIL CHANGE ≤5 psig
RECHARGE FROM DEEP VACUUM
→ EVAPORATOR CHARGING VALVE
→ VAPOR FIRST
→ LIQUID LATER
NORMAL TYPE III ENDPOINT
→ 25 mm Hg ABSOLUTE
QUALIFYING NON-MAJOR OPENING
→ ≤0 psig
SAFETY
→ PRESSURE RELIEF
→ REFRIGERANT MONITORING
→ VENTILATION
→ WATER-SIDE ENERGY CONTROL
References
Project Source Sections
- Section 9.1 - Low-Pressure Appliance Fundamentals
- Section 9.2 - Low-Pressure Chiller Components
- Section 9.3 - Air Moisture and Purge Units
- Section 9.4 - Low-Pressure Leak Detection and Pressurization
- Section 9.5 - Type III Recovery Sequence
- Section 9.6 - Freeze Prevention During Recovery
- Section 9.7 - Refrigerant in Oil
- Section 9.8 - Recharging Low-Pressure Systems
- Section 9.9 - Type III Evacuation Requirements
- Section 9.10 - Type III Safety and Machinery Rooms
- Section 9.11 - Quick Reference
- Section 10.1 - Universal Certification Comparison Tables
- Section 10.2 - High-Priority Numbers and Thresholds
- Section 10.3 - Commonly Confused Terms